| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT******************* | | | | | | 1)NOTE:PLEASE SUBMIT AIC RATINGS FOR ALL | | | EQUIPMENT BEING INSTALLED INCULDING | | | MAIN DISCONNECTS AND PANEL. 110-9/215-5 | | | | | | 2)NOTE: PLEASE SUBMIT PANEL SCHEDULE | | | FOR "C". NOT SHOWN. 215-5 | | | | | | 3)NOTE; PLEASE SEE LOAD CALCULATIONS!!! | | | SQ FT CALCS DO NOT CORRELATE WITH PLANS | | | OR HOUSE BEING BUILT.215-5 | | | | | | 4)NOTE: PLEASE SHOW COLD WATER PIPE PER | | | 250-50 | | | | | | 5)NOTE: PLEASE SEE 210-8 FOR LAUNDRY | | | ROOM REC. | | | | | | 6)NOTE: PLEASE SEE 210-52 FOR OUTLET | | | SPACING. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | CITY OF WEST PALM BEACH | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|