Plan Review Notes
Plan Review Notes For Permit 00080502
Permit Number 00080502
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)SUBMIT OCCUPANT LOAD BASED ON SQ.FEET
 OF HABITABLE FLOOR SPACE.SEE SPC SEC.
 407.1.3. FOR ALLOWED DEDUCTIBLE AREAS.
 ADDITIONAL PLBG.FIXTURES MAY BE REQD.
  
 2)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.DRINKING FOUNTAIN SHALL COMPLY
 W/FACBC SECS.4.1.3,4.15.PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 3)SINK IN LOUNGE SHALL COMPLY W/FACBC
 SEC.4.24.1-4.24.7.MAX.HEIGHT OF CABINET
 SHALL BE 34"AT CLEAR FLOOR ACCESS AREA.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.