| Plan Review Notes For Permit 00080487 |
| Permit Number |
00080487 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. PLAN SHOWS SPACE TO BE NEGATIVE 65CFM | | | FLORIDA ENERGY CODE 410.1 NOTES BUILDING | | | PRESSURIZATION SHOULD BE EITHER NEUTRAL | | | OR POSITIVE TO PREVENT INFILTRATION OF | | | EXCESS LATENT LOAD |
|