| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| | 1-PROVIDE ATTIC ACCESS AT FRONT OF |
| | GARAGE AREA. SEC. 2309.6 SBC 1997. |
| | 2-GENERAL NOTES SHEET TO BE UPDATED AS |
| | REQUIRED. WE USE SBC 1997 AND FLORIDA |
| | ENERGY EFFICIENCY CODE FOR BUILDING |
| | CONSTRUCTION, 1997 EDITION. SEE |
| | COMMENTS ON PLANS. |
| | 3-PROVIDE STRUCTURAL BUCK DETAIL USING |
| | A 2X BUCK AS REQUIRED BY THE PRODUCT |
| | APPROVAL SUBMITTED. |
| | 4-PROVIDE BBQ UL LISTING AND INSTALLAT'N |
| | SPECIFICATIONS. |
| | 5-PROVIDE PRODUCT APPROVAL FOR FIXED |
| | TRANSOM WINDOW WITH THE SIZE SHOWN AS |
| | SHOWN AT FAMILY ROOM. |
| | 6-PROVIDE PRODUCT APPROVAL FOR SLIDING |
| | GLASS DOORS WITH THREE PANELS AND THE |
| | SIZE SHOWN AT FAMILY ROOM. PRODUCT |
| | APPROVAL SUBMITTED DOESN'T COVER THREE |
| | PANELS WITH THE SIZE SHOWN ON PLANS. |
| | 7-PROVIDE STRUCTURAL BUCK DETAIL USING |
| | A 2X BUCK FOR FIXED AND ARCHED WINDOWS |
| | AS REQUIRED BY THE PRODUCT APPROVAL. |
| | 8-SEE PLANS FOR ADDITIONAL COMMENTS. |
| | INCLUDING THOSE BY THE OTHER TRADES. |
| | |
| | |
| | |
| | NOTES: |
| | -IF YOU HAVE ANY QUESTIONS PLEASE CALL |
| | JULIO GOMEZ AT 659-8096 EXT. 8232. |
| | -PLEASE UPDATE ALL PLANS AS REQUIRED TO |
| | AVOID UNNECESSARY RETURNS ON FUTURE |
| | SUBMITTALS. |
| | -PROVIDE INFORMATION REQUESTED ON THIS |
| | PROVISO PRIOR TO INSTALLATION. |