Plan Review Notes
Plan Review Notes For Permit 00080391
Permit Number 00080391
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00****************DENIED*****************
  
 1. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 3. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 TO BE TIED TO BLDG FIRE ALARM OR HORN
 AND STROBE FOR NOTIFICATION PER NFPA
 90A 4-4.4
 NOTE: NO COMBUSTIBLES ALLOWED IN RETURN
 AIR PLENUM