2001-01-08 00:00:001) WRONG LIFE SAFETY CODE REFERENCED
 SHOULD READ 1985 LIFE SAFETY CODE
 INSTEAD OF 1991 LIFE SAFETY CODE.
 2) NO FIRE SPRINKLER DRAWINGS SUBMITTED
 WITH PLANS.
 3) ALTHOUGH THE TENANT SPACE OCCUPANT
 LOAD IS LESS THAN 50 AND THE REAR EXIT
 DOOR IS NOT REQUIRED TO SWING IN THE
 DIRECTION OF EXIT TRAVEL, DOES
 ANYTHING STOP IT FROM SWINGING OUT.
 4) NO FIRE ALARM DEVICES SHOWN ON
 PLANS. HOW IS THE BASE BUILDING
 FIRE ALARM SYSTEM HEARD.
 5) CLEARLY DEMONSTRATE ALL EMERGENCY
 LIGHTING FIXTURES IN SPACE.
 6) AN ADDITIONAL EXIT SIGN IS NEEDED
 TO DIRECT PERSONS TO REAR EXIT DOOR
 LOCATION.
 7) EXITING THROUGH STOCKROOM PERMITTED
 ONLY IF THE FOLLOWING CONDITIONS EXIST,
 NOT MORE THAN 50 PERCENT OF EXIT ACCESS
 IS ALLOWED THROUGH STOCKROOM, DOOR TO
 STOCKROOM CANNOT BE LOCKED, AN AISLE OF
 AT LEAST 44" TO BE PROVIDED AND
 MAINTAINED.