| Plan Review Notes For Permit 00080391 |
| Permit Number |
00080391 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED | | | SHOULD READ 1985 LIFE SAFETY CODE | | | INSTEAD OF 1991 LIFE SAFETY CODE. | | | 2) NO FIRE SPRINKLER DRAWINGS SUBMITTED | | | WITH PLANS. | | | 3) ALTHOUGH THE TENANT SPACE OCCUPANT | | | LOAD IS LESS THAN 50 AND THE REAR EXIT | | | DOOR IS NOT REQUIRED TO SWING IN THE | | | DIRECTION OF EXIT TRAVEL, DOES | | | ANYTHING STOP IT FROM SWINGING OUT. | | | 4) NO FIRE ALARM DEVICES SHOWN ON | | | PLANS. HOW IS THE BASE BUILDING | | | FIRE ALARM SYSTEM HEARD. | | | 5) CLEARLY DEMONSTRATE ALL EMERGENCY | | | LIGHTING FIXTURES IN SPACE. | | | 6) AN ADDITIONAL EXIT SIGN IS NEEDED | | | TO DIRECT PERSONS TO REAR EXIT DOOR | | | LOCATION. | | | 7) EXITING THROUGH STOCKROOM PERMITTED | | | ONLY IF THE FOLLOWING CONDITIONS EXIST, | | | NOT MORE THAN 50 PERCENT OF EXIT ACCESS | | | IS ALLOWED THROUGH STOCKROOM, DOOR TO | | | STOCKROOM CANNOT BE LOCKED, AN AISLE OF | | | AT LEAST 44" TO BE PROVIDED AND | | | MAINTAINED. |
|