2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW ADDITIONAL EXIT
 LIGHT REQ`D OUTSIDE STORAGE ROOM
  
 2)NOTE:PLEASE HAVE THE '99' NEC REF.ON
 COVER SHEET ALONG WITH THE LOCAL CITY
 OF WEST APLM BEACH AMENDMENTS.
  
 3)NOTE: PLEASE SEE 210-62 FOR SHOW
 WINDOW RECEPT REQ`MENTS.
  
  
 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. (LIGHTING/SIGNAGE/ETC).
  
 5)NOTE: PLEASE SUBMIT MORE DETAIL ON
 THE LOAD CALCULATIONS. SQ.FT ETC
  
 6)NOTE: PLEASEGIVE CLARIFICATION ON
 SPACE 36 FOR DIMMING SYSTEM. 5400VA AT
 120V?? AT 125% FOR CONTINUOUS LOAD.
 BREAKER SIZE TO BE SHOWN AS MIN. REQ`D.
  
 7)NOTE: PLEASE SEE REQ`MENTS OF 220-12B
 FOR TRACK LIGHITNG.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  