Plan Review Notes
Plan Review Notes For Permit 00080385
Permit Number 00080385
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001) THE DIGITAL MESSAGE IS TO ANNOUNCE
 MAY I HAVE YOUR ATTENTION PLEASE, MAY
 I HAVE YOUR ATTENTION PLEASE, AN
 EMERGENCY HAS BEEN REPORTED IN THE
 BUILDING, PLEASE LEAVE THE BUILDING
 BY THE NEAREST EXIT, DO NOT USE THE
 ELEVATORS, REPEAT MESSAGE UNTIL
 SILENCED.
 2) THE SMOKE CONTROL PANEL LED'S APPEAR
 TO INDICATE RED WHEN THE FAN STATUS IS
 OFF. WHEN THE ON/OFF/AUTO SWITCH IS IN
 THE OFF POSITION, THE LED'S SHOULD NOT
 REFLECT A "NORMAL" FAN OFF CONDITION.
 CLARIFY LED STATUS IF SWITCH IS IN THE
 OFF POSITION.
 3) A REMOTE ANNUNCIATOR IS REQUESTED
 FOR THE SECOND LEVEL, MAIN ENTRY
 AREA OF THE MUVICO BUILDING.
 APPROVED PROVISO: