2001-01-08 00:00:001) PLEASE PROVIDE WHAT DIALOGUE IS TO
 BE USED FOR THE TAPED MESSAGE PORTION
 OF THE FIRE ALARM SYSTEM.
 2) SMOKE DETECTORS ARE TO BE INSTALLED
 A MINIMUM OF THREE FEET FROM ANY AIR
 CONDITIONER DIFFUSER.
 3) THERE ARE NO FIRE ALARM DEVICES IN
 THE GRAND PARTY/SPECIAL EVENT ROOM (301)
 4) SMOKE DETECTOR REQUIRED ABOVE FIRE
 ALARM CONTROL PANEL IN ROOM 150A.
 5) MANY LARGE STORAGE ROOM AND OTHER
 SERVICE TYPE ROOMS ARE ABSENT OF SMOKE
 OR HEAT DETECTORS, PLEASE EXPLAIN
 RATIONALE.
 6) NO FIRE ALARM EQUIPMENT NOTED IN
 BOX OFFICES.
 7) THE SMOKE CONTROL SYSTEM DISPLAYED
 ON SHEET 8, WAS REVIEWED BY CHIEF
 MECHANICAL INSPECTOR NANCY DENMARK AND
 THIS WRITER. AFTER A REVIEW OF THE
 NOTES REGARDING THE DAMPERS AND CONTROL
 FANS, WE WERE UNCLEAR OF WHAT LIGHT
 WOULD BE ACTIVATED TO INDICATE FAN
 STATUS OR DAMPER STATUS. PLEASE PROVIDE
 MORE INFORMATION REGARDING SMOKE CONTROL
 SYSTEM. THE DIAGRAM ON SHEET 8 APPEARED
 TO REPRESENT THE BUILDING.
 8) ARE THE TWO BUTTONS BESIDE THE
 CONTROL KNOBS, CAPABLE OF PROVIDING
 THE THREE COLORS AS INDICATED ON THE
 LEGEND.
 9) WHEN THE FIRE ALARM SYSTEM IS
 ACTVIATED, THE ENTIRE BUILDING IS TO
 GO INTO ALARM.
 10) FIRE ALARM SYSTEM TO BE MONITORED
 BY A UL LISTED APPROVED CENTRAL STATION.
 11) PLEASE EXPLAIN WHY FIRE ALARM HOLD
 OPEN DEVICES ARE PRESENT AT THE
 AUDITORIUM.