| Plan Review Notes For Permit 00080356 |
| Permit Number |
00080356 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) FABRIC AWNING TO BE FIRE RETARDANT. | | | 2) PROVIDE FIRE ALARM SYSTEM PLANS AND | | | PERMIT FOR FIRE ALARM EQUIPMENT SHOWN | | | ON DRAWINGS. | | | 3) INTERIOR FINISH ON WALLS AND CEILINGS | | | SHALL BE CLASS A OR B. ON 8.15.00, | | | WRITER SPOKE TO BOB FLOOD OF REG | | | REFERENCE THE PLANS. | | | 4) TRAVEL DISTANCE PERMITTED UNDER THE | | | PREVAILING FIRE CODE ALLOWS FOR ONLY | | | 150 FEET IF SPRINKLERS ARE PRESENT. THIS | | | IS MORE STRINGENT THAN THE 250 FEET | | | REFERENCED. | | | 5) TWO ADDITIONAL EXIT SIGNS NEEDED TO | | | DIRECT PERSONS TO REAR EXIT. | | | 6) EXITING PERMITTED THROUGH STOCKROOM | | | IF THE FOLLOWING CONDITIONS EXIST, NOT | | | MORE THAN 50 PERCENT OF EXIT ACCESS IS | | | PROVIDED THROUGH STOCKROOM, DOOR | | | LEADING TO STOCKROOM CANNOT BE SUBJECT | | | TO LOCKING, AN AISLE OF AT LEAST 44" | | | BE PROVIDED, AND THIS AISLE IS TO | | | BE MAINTAINED. | | | 7) PORTABLE FIRE EXTINGUISHERS REQUIRED. |
|