2001-01-08 00:00:001) ENTIRE SPACE TO BE PROTECTED BY
 FIRE SPRINKLERS. THIS INCLUDES ALL
 ELECTRICAL, MECHANICAL, AND SERVICE
 ROOMS.
 2) WATER CURTAIN PROVIDED TO PROTECT
 ESCALATOR OPENING TO COMPLY WITH
 NFPA 13 REQUIREMENTS. SPRINKLER HEADS
 TO BE NO MORE THAN SIX FEET APART.
 3) FIRE SPRINKLER PROTECTION REQUIRED
 UNDERNEATH ESCALATOR.
 4) NO FIRE SPRINKLER HEAD SHOWN IN
 ELEVATOR MACHINE ROOM.
 5) FIRE SPRINKLER SYSTEM INSTALLATION
 TO COMPLY WITH NFPA 13.