Plan Review Notes
Plan Review Notes For Permit 00080302
Permit Number 00080302
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00FLOOR DRAINS ARE NOT PROPERLY VENTED.
 CONNECT SEPARATELY TO THE VENTED BUILD-
 DRAIN.SPC SEC.901.2.,908.2,TABLE 908.1.
  
 2)A GATE VALVE IS REQD.ON THE DISCHARGE
 PIPING OF THE SUMP PER SPC SEC.717.2.
  
 3)SUMP SHALL BE VENTED PER SPC SEC.717.6
  
 4)CONNECTION TO THE BUILDING DRAINAGE
 SYSTEM SHALL COMPLY W/SPC SEC.717.11.
  
 5)PUMP SHALL BE LISTED AND COMPLY W/SPC
 303.1,303.3,303.5.
  
 6)A MAIN STACK MIN.OF 3"IS REQD.PER SPC
 904.3.