Plan Review Notes
Plan Review Notes For Permit 00080291
Permit Number 00080291
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW EQUIPMENT BEING INSTALLED. MUST BE
 RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110-9. 215-5
  
 2)NOTE: PLEASE INCLUDE NEW BLDG. STEEL
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM. 250-50
  
 3)NOTE: PLEASE NOTE THAT MORE THAN 50%
 OF NEW BLDG.SMOKE DETECTORS WILL BE
 REQ`D INSIDE AND OUTSIDE EXISTING SLEEP-
 -ING ROOMS. PER NFPA-72 2-2.1.1.1 ,97
 BLDG. CODE AND FL. STATUES.
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL NEW SLEEPING ROOMS.
  
 4)NOTE: PLEASE NOTE THAT ALL EXISTING
 BATHS AND KITCHEN COUNTERSPACE, AND
 GARAGE OUTLETS WILL NEED TO MEET 210-8
 OF THE NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLANS WOULD HAVE PASSED WITH A
 PROVISO BUT WERE COMING BACK FOR
 BLDG COMMENTS. IF THERE ARE ANY QUESTION
 -S PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372