Plan Review Notes
Plan Review Notes For Permit 00080288
Permit Number 00080288
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CHECKLIST:
 1-LEFT HAND SIDE ELEVATION EXCEEDS THE
 PERCENTAGE OF OPENINGS ALLOWEDBY
 TABLE 600, SBC 1997.
 2-PROVIDE ATTIC ACCESS AT PORTE COCHER,
 FOYER, RIGHT WING GARAGE AREA AND ALL
 CUPOLAS. SECTION 2309.6 SBC 1997.
 -PROVIDE COMPLETE METAL FRAMING DETAILS
 AND SECTIONS AT ATTIC SPACES WITH AHU
 EQUIPMENT. INCLUDING AHU'SANCHORING
 SPECIFICATIONS AND DETAILS.
 3-ARCHITECT NEED TO DATE DRAWINGS AT
 AT THE TIME OF SEALING THEM. FLORIDA
 STATUTES, CHAPTER 481.
 4-PROVIDE A SITE PLAN WITH DIMENSIONS OR
 SURVEY WITH BUILDING LAYOUT.
 -NOTE: SURVEYOR TO PROVIDE ORIGINAL
 SIGNATURE AND DATE ON ANY DOCUMENT TO
 BE FILED FOR PUBLIC RECORDS. CHAPTER
 471 OF FLORIDA STATUTES.
 5-ARCHITECT TO REVISE/UPDATE ALL DWGS AS
 REQUIRED. USE SBC 1997 AND FLORIDA
 ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION. GET FAMILIAR WITH THIS
 CODES AND REFERENCE THE APPROPIATE
 STANDARDS AS DONE IN THESE CODES.
 -SEE PLANS FOR COMMENTS.
 6-PROVIDE COMPLETE FRAMING DETAILS AT
 ARCHED WINDOWS MULLED TOGETHER AT
 BREAKFAST AREA. SEC. 104.2.2 CITY
 AMENDMENTS.
 7-PROVIDE SAFETY GLASS WHERE REQUIRED.
 SECTION 2405.2 SBC 1997. SEE PLANS.
 8-PROVIDE MINIMUM ONE BATHROOM WITH A
 DOOR THAT ALLOWS 29" MIN. CLEAR OPEN'G
 SECTION 11 OF FLORIDA ACCESSIBILITY
 CODE FOR BUILDING CONSTRUCTION,1997 ED
 9-PROVIDE SIZE OF CEILING FANS. SEE
 TABLE 6-6 OF FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING CONSTRUCTION,1997 ED
 10-PROVIDE COMPLETE SPECIFICATIONS AND
 DETAILS FOR CEILING CONSTRUCTION AT
 PORTE COCHER, ENTRY AND REAR PORCHES.
 INCLUDING FASTENER TYPES AND SPACING.
 SECTION 2504 SBC 1997.
 11-PROVIDE COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS FOR SCREEN ENCLOSURE IN
 COVERED PATIO BY MASTER BEDROOM.
 NOTE: INCLUDE SCREENED CEILING.
 SECTION 104.2.2 CITY AMENDMENTS.
 12-PROVIDE COMPLETE SECTION/DETAIL THRU
 CHIMNEY. SPECIFY ALL CONNECTORS.
 SECTION 104.2.2 CITY AMENDMENTS.
 13-PROVIDE COMPLETE FRAMING DETAILS/
 SECTIONS AND SPECIFICATIONS FOR
 CONSTRUCTION OF KNEE WALLS AND CUPOLAS
 SECTION 104.2.2 CITY AMENDMENTS.
 14-PROVIDE COMPLETE SECTION/DETAIL FOR
 ATTACHMENT OF WINDOWS TO STEEL COLUMN
 IN MASTER BATHROOM. SECTION 104.2.2
 15-ROOF FRAMING PLAN:
 -PROVIDE ANCHOR SCHEDULE FOR WOOD TO
 WOOD CONNECTIONS.
 -SHOW CRICKET LOCATIONS AND CONSTRUCT'N
 SECTION 104.2.2 CITY AMENDMENTS.
 16-PROVIDE MORE INFORMATION FOR BBQ
 CONSTRUCTION. IS IT MASONRY OR PRE-
 MANUFACTURED. COMPLY WITH SECTION 2808
 OR 2114.4 AS REQUIRED.
 17-PROVIDE THE DESIGN PRESSURES THAT
 WERE CALCULATED FOR EXTERIOR OPENINGS
 FOR GARAGE DOORS.AND FOR THOSE OPENIGS
 NOT SHOWN ON EXTERIOR ELEVATIONS.
 NOTE: EXPLAIN WHY THE GARAGE DOOR
 DESIGN PRESSURES IN PRODUCT APPROVAL
 DRAWINGS WERE ERASED OR DELETED.
 18-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS WITH SIDELITE ASSEMBLY, GARAGE
 DOORS, 4 PANELS FRENCH DOORS, FRENCH
 DOORS WITH TRANSOM ABOVE ASSEMBLIES,
 ROUND WINDOWS, FIXED WINDOWS LARGER
 THAN THE ONE SHOWN IN PRODUCT APPROVAL
 SUBMITTED AND LIVING ROOM LARGE WINDOW
 ASSEMBLY.
 19-SEE COMMENTS BY OTHER TRADES.
 20-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. MEAN
 ROOF HEIGHT IS +/- 33'-8".
  
  
 NOTES:
 -PLEASE RETURN REVIEWED SET AFTER ALL
 REVISIONS ARE DONE TO ORIGINAL DRAWINGS
 IN ORDER TO EXPEDITE THE REVIEW PROCESS
 -IF YOU HAVE ANY QUESTIONS, PLEASE FEEL
 FREE TO CALL JULIO GOMEZ AT 659-8096
 EXT. 8232.