| 2001-01-08 00:00:00 | **************** UNSAT***************** |
| | |
| | 1)NOTE: PLEASE HAVE BLDG. STEEL AS PART |
| | OF THE GROUNDING ELECTRODE SYSTEM PER |
| | 250-50 |
| | |
| | 2)NOTE: PLEASE SEE THAT PANEL "A" IS NOT |
| | COMPLETE. WIRE/KVA/BRKR ETC. |
| | |
| | 3)NOTE: PLEASE SHOW CLARIFICATION ON |
| | HOW MANY A/C SYSTEMS ARE GOING TO BE |
| | INSTALLED. PANEL SCHEDULES SHOW 3 UNITS |
| | AND PLANS SHOW 4 UNITS?? |
| | ADJUST LOAD CALCULATIONS. |
| | |
| | 4)NOTE: PLEASE SEE PANEL "B" PLEASE |
| | NOTE THAT ALL WIRE SIZES MUST BE SUFF. |
| | FOR LOADS SHOWN. 310-16 |
| | |
| | 5)NOTE: PLEASE LIST THE REQ`D DEDICATED |
| | BATH(S) CIRCUIT(S) PER 210-11-C-3 |
| | |
| | 6)NOTE: PLEASE SEE 210-52-C-3 FOR |
| | KITCHEN ISLAND RECPECTS. |
| | |
| | 7)NOTE: PLEASE SEE 210-52 FOR OUTLET |
| | SPACING. |
| | |
| | 8)NOTE: PLEASE BATH BY FRONT ENTRANCE |
| | FOR OUTLET IN BATH TO BE INSTALLED |
| | NEXT TO SINK PER 210-52D |
| | |
| | 9)NOTE: PLEASE SHOW OUTLETS IN ALL BATHS |
| | AS GFI/GFI PROTECTED.PER 210-8 |
| | |
| | 10)NOTE: PLEASE SHOW AND GIVE MORE |
| | DETAIL ON ROOM NEXT TO GARAGE. ROOM IS |
| | SHOWN BUT NOT LABELED. NO ELECTRICAL |
| | SHOWN FOR LIGHTING OR GFI.??? |
| | |
| | 11)NOTE: PLANS CAN NOT BE ACCEPTED WITH |
| | CHANGES HAND DRAWN IN UNLESS EACH |
| | CHANGE IS SIGNED AND DATED BY ARCH.OR |
| | ENG. OF RECORD. THIS IS A STATE STATUE. |
| | |
| | 12)NOTE: THE AIC RATING OF 22,000IS |
| | SHOWN. IS THIS FOR MAIN DISCONNECTS? OR |
| | IS THIS FOR PANELS ALSO? PLEASE HAVE THE |
| | AIC RATINGS LISTED ON EACH PANEL SCHED- |
| | -ULE AND DISCONNECT ALONG WITH INFORMAT- |
| | -ION FOR PANEL SPECS. |
| | |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | 561-659-8096 EXT 8372 |