Plan Review Notes
Plan Review Notes For Permit 00080255
Permit Number 00080255
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)THE NUMBER OF REQUIRED MINIMUM PLUMB-
 ING FIXTURES SHALL COMPLY W/SPC TABLE
 407.SEE SPC SEC.407.1.3.FOR ALLOWED
 DEDUCTIBLE AREAS.AN ADDITIONAL WATER
 CLOSET AND LAVATORY IS REQD.FOR THE
 FEMALES.
  
 2)H.C.DRINKING FOUNTAIN SHALL COMPLY W/
 FACBC SEC.4.1.3,4.15.PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BEND-
 ING OR STOOPING.
  
 3)SUBMIT MANUF.SHEETS FOR AUTO PROCESSOR
 INFORMATION REQD.ON TYPES AND AMOUNTS OF
 CHEMICALS USED.A NEUTRALIZINGTANK MAY
 BE REQD.PER SPC SEC.801.4.
  
 4)SHT.P-2.SIZE THE COMPRESSED AIR
 DIAGRAM.INCLUDE BRANCHES TO CHAIRS.
  
 5)SHT.P-2-INDICATE SIZE OF BRANCHES TO
 CHAIRS.
  
 6)AIR COMPRESSOR INTAKE SHALL BE LOCATED
 WHERE NO CONTAMINATION FROM VACUUM
 SYSTEM DISCHARGES IS ANTICIPATED.NFPA
 99 SEC.4-5.1.1.3.
  
 7)ACCESSIBLE CLEANOUTS ARE REQD.IN THE
 VACUUM SYSTEM PER NFPA 99 SEC.4-5.2.2.1.
  
 8)SUBMIT WATER RISER DIAGRAM FOR ALL
 PLUMBING WORK BEING INSTALLED.
  
 9)SEPARATE PERMIT REQD.FOR MEDICAL GAS.
 SUBMIT PLANS,MANUF.INSTALLATION REQS.ETC
 AT TIME OF APPLICATION.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved