2001-01-08 00:00:001) DEMOLITION OPERATIONS TO COMPLY
 WITH NFPA 241, THE STANDARD FOR
 BUILDINGS UNDER CONSTRUCTION, ALTERATION
 AND DEMOLITION OPERATIONS.
 2) WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ LIFE SAFETY CODE 1985
 EDITION INSTEAD OF LIFE SAFETY CODE
 1997 EDTION.
 3) PROVIDE FIRE ALARM SYSTEM DRAWINGS
 FOR FIRE ALARM EQUIPMENT SHOWN ON
 PLANS. A SEPARATE PLAN AND PERMIT IS
 REQUIRED.
 4) PROVIDE PLAN AND PERMIT FOR ANY FIRE
 SPRINKLER SYSTEM REMODEL DONE TO THE
 EXISTING FIRE SPRINKLER SYSTEM IN
 TENANT SPACE.