| Date |
Text |
| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-PAY IMPACT FEES. TAKE DRAWINGS TO THE |
| | PALM BEACH COUNTY BUILDING (AUSTRALIAN |
| | AND SOUTHERN BLVD). THEY WILL STAMP |
| | DRAWINGS AND WILL GIVE YOU A RECEIPT. |
| | 2-PROPOSED ADDITION WILL BE NEXT TO AN |
| | EXISTING METAL BUILDING. SHOW HOW |
| | COMPLYING WITH TABLE 600 OF SBC 1997 |
| | FOR FIRE RATING AND PERCENTAGE OF |
| | OPENINGS ALLOWED. |
| | -PROVIDE ALL DIMENSIONS IN SITE PLAN: |
| | DISTANCE BETWEEN BUILDINGS AND REAR |
| | PROPERTY LINE. |
| | 3-PROVIDE ATTIC ACCESS.SEC 2309.6 SBC/97 |
| | 4-PROVIDE SPECIFICATIONS FOR ATTACHEMENT |
| | OF PLYWOOD ROOF SHEATHING AND T-1-11 |
| | EXTERIOR WALL COVERING. SECTION 2306 |
| | CITY AMENDMENTS. |
| | 5-SPECIFY SIZE OF EXISTING FOOTING. |
| | NOTE: FOOTING TO BE MINIMUM 12" BELOW |
| | GRADE AND 4" ABOVE GRADE AS PER SECT'N |
| | 1804.1.9 CITY AMENDMENTS AND SECTION |
| | 1804.1.3 SBC 1997. |
| | 6-SPECIFY CALCULATED DESIGN PRESSURES AT |
| | ALL EXTERIOR OPENINGS. SEC 1606 SBC/97 |
| | 7-WALL SECTION: |
| | -PROVIDE 1 1/2" WATER STOP. SECTION |
| | 2111.6 CITY AMENDMENTS. |
| | 8-PROVIDE COMPLETE DETAIL AND SPECS FOR |
| | CONSTRUCTION OF GABLE END. SECTION |
| | 104.2.2 CITY AMENDMENTS. |
| | 9-PROVIDE THE FOLLOWING INFORMATION: |
| | -ROOF PITCH. |
| | -WINDOW SIZES |
| | SECTION 104.2.2 CITY AMENDMENTS. |
| | 10-ENERGY CALCULATIONS: |
| | -FILL COMPLETELY, INCLUDING PAGE TWO. |
| | -ARCHITECT TO SIGN, SEAL AND DATE FORM |
| | AS REQUIRED BY CHAPTER 481 FL. ST. |
| | 11-BEDROOM AND BATHROOM TO COMPLY WITH |
| | THE MINIMUM REQUIREMENTS FOR LIGHT AND |
| | VENTILATION. SEE SECTIONS 1203.1.2, |
| | 12031.4 AND SECTION 1203.4.2 SBC 1997. |
| | 12-SPECIFY CEILING HEIGHTS. SECTION |
| | 1203.2 SBC 1997. |
| | 13-CLARIFY IF RE-ROOFING ENTIRE HOUSE. |
| | SEE WALL SECTION. |
| | 14-PROVIDE HOW ARE OPENINGS FRAMED TO |
| | RECEIVE STORM PANELS.SEC 104.2.2 CITY |
| | AMENDMENTS. |
| | 15-PRODUCT APPROVALS: |
| | -STORM PANELS: |
| | *PROVIDE A KEY PLAN AND A COMPLETE |
| | INSTALLATION SCHEDULE. SEE ATTACHED. |
| | *DRAWINGS NEED TO BE SIGNED AND SEALED |
| | TO BE VALID FOR PERMIT. SEE NOTE #10 |
| | OF GENERAL NOTES. PAGE 1 OF 5. |
| | -EXTERIOR DOOR PRODUCT APPROVAL IS |
| | EXPIRED. |
| | -SINGLE HUNG PRODUCT APPROVAL DRAWINGS |
| | ARE NOT LEGIBLE. |
| | 16-CONSTRUCTION VALUE DECLARED IS TOO |
| | LOW. VALUE WILL BE RE-ADJUSTED GIVING |
| | A MORE REALISTIC NUMBER. |
| | |
| | |
| | NOTES: |
| | -CONSTRUCTION VALUE DECLARED IS TOO LOW. |
| | CONSTRUCTION VALUE WILL BE ADJUSTED |
| | WITH A MORE REALISTIC NUMBER. OWNER |
| | WILL NEED TO RECORD A NOTICE OF |
| | COMMENCEMENT. |
| | -IF YOU HAVE ANY QUESTIONS, PLEASE FEEL |
| | FREE TO CALL JULIO GOMEZ AT 659-8096 |
| | EXT. 8232. |