| Plan Review Notes For Permit 00080152 |
| Permit Number |
00080152 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** PROVISO *************** | | | | | | 1)NOTE: SINCE FIRST REVIEW YOU ARE NOW | | | SHOWING A COMPLETE NEW SERVICE RISER. | | | PLEASE SUBMIT AIC RATINGS OF EQUIPMENT | | | MAINS AND PANELS BEING INSTALLED. | | | PER 110-9 AND 215-5 | | | | | | 2)NOTE: PLEASE SUBMIT COMPLETE REVISED | | | PANEL SCHEDULES.215-5 | | | | | | 3)NOTE: PLEASE CLARIFY WIRE FEEDING | | | 125A PANEL. SHOWS 3# L.?? | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW BEFORE FINAL ELECTRICAL | | | INSPECTION IS CALLED IN. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 659-8096 EXT 8372 |
|