| 2001-01-08 00:00:00 | ************** UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATING FOR |
| | ALL EQUIPMENT BEING INSTALLED. MAINS/ |
| | PANELS MUST BE RATED FOR THE AVAILABLE |
| | FAULT CURRENT.110-9/215-5 |
| | |
| | 2)NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED. 210-8-A-6 |
| | |
| | 3)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE |
| | AND OUTSIDE ALL SLEEPING ROOMS AND ON |
| | EACH LEVEL OF MULTI-LEVEL RES. |
| | |
| | 4)NOTE: PLEASE SEE 210-52-C-3 FOR REQ`D |
| | PENINSULAR RECEPT. |
| | |
| | 5)NOTE: PLEASE LABEL ALL GARAGE REC`S |
| | AS GFI/GFI PROTECTED. 210-8 |
| | |
| | 6)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | SYSTEM. SEE 250-50 FOR REQ`D POINTS OF |
| | GROUND.ALSO INCLUDE SIZE OF GROUNDING |
| | ELECTRODE SIZE PER 250-66 |
| | |
| | 7)NOTE: PLEASE SHOW WIRE SIZES FOR FEED- |
| | -ERS FROM METER TO MAIN PANEL. |
| | |
| | 8)NOTE ;PLEASE INCLUDE THE REQ`D DEDI- |
| | -CATED BATH(S) CIRCUIT(S) PER 210-11-C-3 |
| | ON PANEL SCHEDULE. |
| | |
| | 9)NOTE: PLEASE SEE LOAD CALCULATIONS FOR |
| | HEAT KW., SHOWS 56% MUST BE TYPE -O |
| | LOAD SHOWN IS CORRECT., |
| | |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | |
| | 561-659-8096 EXT 8372 |