| Plan Review Notes For Permit 00080127 |
| Permit Number |
00080127 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ******************PROVISO*************** | | | 1)FIXTURES DOWNSTREAM OF WATER CLOSETS | | | SHALL BE VENTED.SPC SEC.913.2. | | | | | | 2)SINKS ARE NOT PROPERELY VENTED.SPC SEC | | | 901.2. | | | | | | 3)SUBMIT REVISED SANITARY RISER DIAGRAM | | | PRIOR TO PLUMBING INSPECTION. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|