2001-11-03 00:00:00*************BUILDING UNSAT*************
  
 1) THE GLAZING IN THE RELOCATED BATHROOM
 WINDOW IS REQUIRED TO BE SAFETY GLASS
 PER 97 SBC SEC.2405.2.1 (3), WHEN
 LOCATED WITHIN A 24-INCH RADIUS OF A
 DOOR IN THE CLOSED POSITION. PLEASE
 INDICATE ON PLANS.
  
 2) PROVIDE MANUFACTURERS SPECIFICATIONS
 FOR GLASS BLOCK (2 COPIES). PROVIDE (2)
 DRAWINGS INDICATING STRUCTURAL DETAILS
 OF GLASS BLOCK WALL INSTALLATIONS WHICH
 SHOW STRUCTURAL SUPPORTS, JOINT
 REINFORCEMENT, ETC. THE GLASS BLOCK
 SHALL HAVE A MINIMUM THICKNESS OF 3" AT
 THE MORTAR JOINT AND ALL THE MORTAR-
 BEARING SURFACES SHALL BE TREATED FOR
 MORTAR BONDING. 97SBC SEC.2112. WHEN
 INSTALLED IN HAZARDOUS LOCATIONS GLASS
 BLOCK IS REQUIRED TO HAVE A UNIFORM FACE
 THICKNESS OF 0.25 INCH PER 97SBC SECTION
 2405.2.2 (5). PLEASE INDICATE SPECIFIC
 TYPE OF GLASS BLOCK THAT IS TO BE
 INSTALLED.
  