| Plan Review Notes For Permit 00080012 |
| Permit Number |
00080012 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-11-03 00:00:00 | *************BUILDING UNSAT************* | | | | | | 1) THE GLAZING IN THE RELOCATED BATHROOM | | | WINDOW IS REQUIRED TO BE SAFETY GLASS | | | PER 97 SBC SEC.2405.2.1 (3), WHEN | | | LOCATED WITHIN A 24-INCH RADIUS OF A | | | DOOR IN THE CLOSED POSITION. PLEASE | | | INDICATE ON PLANS. | | | | | | 2) PROVIDE MANUFACTURERS SPECIFICATIONS | | | FOR GLASS BLOCK (2 COPIES). PROVIDE (2) | | | DRAWINGS INDICATING STRUCTURAL DETAILS | | | OF GLASS BLOCK WALL INSTALLATIONS WHICH | | | SHOW STRUCTURAL SUPPORTS, JOINT | | | REINFORCEMENT, ETC. THE GLASS BLOCK | | | SHALL HAVE A MINIMUM THICKNESS OF 3" AT | | | THE MORTAR JOINT AND ALL THE MORTAR- | | | BEARING SURFACES SHALL BE TREATED FOR | | | MORTAR BONDING. 97SBC SEC.2112. WHEN | | | INSTALLED IN HAZARDOUS LOCATIONS GLASS | | | BLOCK IS REQUIRED TO HAVE A UNIFORM FACE | | | THICKNESS OF 0.25 INCH PER 97SBC SECTION | | | 2405.2.2 (5). PLEASE INDICATE SPECIFIC | | | TYPE OF GLASS BLOCK THAT IS TO BE | | | INSTALLED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|