| Plan Review Notes For Permit 00080005 |
| Permit Number |
00080005 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** REDLINED ************** | | | | | | 1)NOTE: COLOR CODING FOR FEEDERS IS NOT | | | CORRECT. FIRST REVIEW REFERS TO LOCAL | | | AMENDMENTS FOR FEEDER COLOR CODING FOR | | | 277/480. | | | | | | 2)NOTE: ALSO PLEASE SEE 450-21-B FOR | | | THE EXCEPTION ON TRANSFORMER INSTALLAT- | | | -ION REQ`MENTS. |
|