| Plan Review Notes For Permit 00080005 |
| Permit Number |
00080005 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)DOOR #109 CANNOT SWING INTO CLEAR | | | FLOOR SPACE FOR LAV.FACBC 4.22.2. | | | | | | 2)BENCH IN HANDICAP FITTING ROOM SHALL | | | COMPLY W/FACBC 4.35.4.(17-19" AFF). | | | | | | 3)MAX.HT.TO TOP OF HANDICAP LAV.SHALL BE | | | 34",NOT MIN.SHT.TOO2. | | | | | | 4)A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407.FOUNTAIN SHALL BE HANDICAP | | | ACCESSIBLE AND COMPLY W/FACBC SEC.4.1.3 | | | (10)(A).PROVISIONS SHALL BE MADE FOR | | | PEOPLE WHO HAVE TROUBLE BEMDING OR | | | STOOPING. | | | | | | 5)REVISE HT.OF T.P. DISPENSER.(19"TO | | | CENTER,NOT 17".SHT.T002. | | | | | | 6)MIRROR IN H.C.DRESSING ROOM SHALL | | | COMPLY W/FACBC SEC.4.35.4. | | | | | | 7) FLOOR DRAINS ARE REQD.IN THE TOILET | | | ROOMS PER SPC SEC.409.4.1.1. | | | | | | 8)SUBMIT UL ASSEMBLY NUMBER FOR FIRE | | | SAFING DETAILS PER COUNTYWIDE AMENDMENTS | | | TO SPC SEC.104.2.4.(SHT.T005) | | | | | | 9)FLOORS AND WALLS IN TOILET ROOMS SHALL | | | BE NONABSORBENT TO 4'PER SBC SEC.1204.2. | | | | | | 10)DRY VENTS NOT PERMITTED ON SAN.SYSTEM | | | PER SPC SEC.906.2.1. | | | | | | 11)SIZE OF HANDICAP TOILET STALL SHALL | | | COMPLY W/FACBC SEC.4.17.3.(MIN.83"). |
|