Plan Review Notes
Plan Review Notes For Permit 00080005
Permit Number 00080005
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED:
 *PROVIDE DAMPERS LOCATION AND DETAIL AS
 PER 1997 SMC 610.1.2....
 *PROVIDE AIR BALANCE SCHEDULE PER 1997
 SMC 501.2....
 *PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89....
 *REQUIRE DUCT MATERIAL SCHDULE PER
 FLORIDE ENERGY CODE....
 *BATHROOMS VENTILATION REQUIRED AS PER
 1997 SMC 503.3.1.....
 *INDICATE SMOKE DETECTOR ON PLANS.
 NOTES:
 FAN SHUT-DOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION BY FIRE ALARM SYSTEM
 OR TIED-IN TO HORN AND STROBE AS PER
 NFPA 90A 4.4.4.2. AND 4.4.4.3.....