| 2001-01-08 00:00:00 | ************* UNSAT ******************* | | | | | | 1)NOTE: PLEASE SEE LOAD CALCULATIONS | | | SHOWN ON E-4. THE LOADS SHOWN FOR TRACK | | | LIGHTING DOES NOT SEEM TO CORRELATE | | | WITH LOADS SHOWN ON PANEL SCHEDULES OF | | | LPA/LP AND NONE SHOWN ON "DP". PLEASE | | | CLARIFY. | | | | | | 2)NOTE: PLEASE SEE 450-9 AND 450-21 | | | OF NEC FOR REQ`MENTS FOR TRANSFORMER | | | IN ELECTRICAL ROOM. | | | | | | 3)NOTE: PLEASE SEE LOCAL CODE 210-50 FOR | | | OUTLET SPACING IN STORAGE AREAS. EVERY | | | 20` OF UNENCUMBERED WALL SPACE. | | | MALL STORAGE AREA SHOWN. | | | 4)NOTE:PLEASE SUBMIT AIC RATINGS FOR ALL | | | EQUIPMENT/ PANELS AND DISCONNECTS. | | | ALL MUST BE RATED FOR THE AVAILABLE | | | FAULT CURRENT PER 110-9/ 215-5 | | | | | | 5)NOTE: PLEASE NOTE COLOR CODING FOR | | | ALL FEEDERS PER LOCAL CODE 215 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW, IF THERE ARE ANY QUESTIONS | | | PLEASE CALL, | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|