| Plan Review Notes For Permit 00080005 |
| Permit Number |
00080005 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1.SUBMIT FIRE SPRINKLER PLANS AND | | | APPLICIATION FOR PERMIT. FIRE SPRINKLER | | | PERMIT MUST BE ISSUED PRIOR TO BUILDING | | | PERMIT ISSURANCE. | | | 2.PROVIDE PRODUCT APPROVAL FOR IMPACT | | | RESISTANT GLAZING FOR WINDOWS AND DOORS | | | FOR STOREFRONT. METRO DADE COUNTY OR | | | SBCCI SSTD12-96. | | | 3.SIGNS REQURIES SEPERATE PERMITS. | | | 4.NOTE: ALL WOOD BLOCKING TO BE FIRE | | | RETARDANT. | | | 5. TITLE SHEET- PROJECT DATA-THE STORAGE | | | ROOM ON THE SECOND FLOOR IS A SEPERATE | | | OCCUPANCY (USE GROUP)SINCE IT IS NOT | | | ATTACHED TO MAIN TENANT SPACE. THIS AREA | | | REQUIRES 2 HOUR FIRE SEPERATION. PROVIDE | | | UL ASSEMBLY NUMBER AND BOTH SIDES MUST | | | BE FINISHED. | | | 6.DEMIZING WALL-GENERAL NOTE ON SHEET | | | A101 READS AS IF TENANT SIDE ONLY | | | COMPLETED ONLY-PARTITION DETAIL CALLS | | | FOR A COMPLETED ASSEMBLY FOR 1 HOUR | | | FIRE RATED CONSTRUCTION- BOTH SIDES MUST | | | BE COMPLETED PRIOR TO C.O. BEING ISUED. | | | 7.TITLE SHEET-PROJECT DATA | | | A)AMEND LSC 1991 TO 1985 NFPA 101 | | | B)AMEND 1994 SBC TO 1997 SBC WITH | | | 1999 CITY AMENDMENTS. |
|