| 2001-01-08 00:00:00 | DENIED |
| | |
| | 1)OWNER OR AGENT MUST SIGN ENERGY FORMS. |
| | |
| | 2)SITE SPECIFIC PRODUCT APPROVALS FOR |
| | WINDOWS THAT WERE SUBMITTED MUST HAVE |
| | ORIGINALWET SIGNATURE, DATE AND |
| | IMPRESSION SEAL OF ENGINEER CERTIFYING |
| | THE PRODUCT CONFORMS TO 97 SBC AND THE |
| | SAME INFORMATION MUST BE PROVIDED BY AN |
| | ARCHITECT OR ENGINEER CERTIFYING THE |
| | PRODUCT IS SUFFICIENT FOR THE PROJECT |
| | SITE. |
| | |
| | 3)PROVIDE KEY PLAN AND INSTALLATION |
| | SCHEDULE INDICATING SPECIFIC ANCHORS TO |
| | BE USED FOR STORM PANELS. |
| | |
| | 4)PERCENTAGE OF WALL OPENINGS ALLOWED |
| | PER TABLE 600 OF 97 SBC ARE EXCEEDED ON |
| | SOUTH AND EAST ELEVATIONS. NOTE:THE |
| | HEIGHT OF THE WALL IS THE DISTANCE FROM |
| | FINISH FLOOR TO THE CEILING OF EACH |
| | STORY. PLEASE CORRECT. |
| | |
| | 5)PROVIDE 2 CURRENT COPIES OF METRO-DADE |
| | OR SBCCI PRODUCT APPROVALS FOR INSWING |
| | FRENCH DOORS. |
| | |
| | 6)PROVIDE FASTENING DETAILS FOR ATTACH- |
| | ING PT WOOD BUCKS TO MASONRY AT WINDOW |
| | AND DOOR OPENINGS. SPECIFY THE TYPE OF |
| | ANCHOR AND ANCHOR SPACING. |
| | |
| | 7)ONE OF THE WINDOWS SHOWN ON THE WEST |
| | ELEVATION IS NOT INDICATED ON THE FLOOR |
| | PLAN. PLEASE CLARIFY. |
| | |
| | 8)DESIGN COMPLIANCE FORM MUST BE WET |
| | SIGNED,SEALED AND DATED BY AN ARCHITECT |
| | OR ENGINEER OR THE INFORMATION CAN BE |
| | LISTED ON THE PLANS AS NOTES. IF NOTED |
| | ON PLANS FORM IS NOT REQUIRED. |