| 2001-01-08 00:00:00 | DENIED |
| | |
| | 1)IMPACT FEES MUST BE PAID TO PALM BEACH |
| | COUNTY,PLANS STAMPED BY THEM AND COPY OF |
| | RECEIPT SUBMITTED TO CITY OF W.P.B. |
| | BUILDING DEPARTMENT. |
| | |
| | 2)PROVIDE 2 CURRENT COPIES OF METRO-DADE |
| | OR SBCCI PRODUCT APPROVALS FOR EACH |
| | SPECIFIC TYPE OF EXTERIOR WINDOW,DOOR, |
| | AND WINDOW MULLIONS TO BE USED. |
| | |
| | 3)PROVIDE 2 CURRENT COPIES OF METRO-DADE |
| | OR SBCCI PRODUCT APPROVALS FOR ROOFING |
| | MATERIALS OR SUBMIT WITH SEPARATE ROOF |
| | PERMIT APPLICATION. |
| | |
| | 4)IMPACT PROTECTION IS REQUIRED ON ALL |
| | EXTERIOR GLAZED OPENINGS. COUNTYWIDE |
| | AMENDMENTS TO 97 STANDARD BUILDING CODE. |
| | |
| | 5)PROVIDE 2 CURRENT COPIES OF METRO-DADE |
| | OR SBCCI PRODUCT APPROVALS FOR STORM |
| | PANELS,KEY PLANS AND INSTALLATION |
| | SCHEDULE INDICATING SPECIFIC ANCHORS TO |
| | BE USED. |
| | |
| | 6)PERCENTAGE OF ALLOWABLE WALL OPENINGS |
| | PER TABLE 600 IN 97 SBC ARE EXCEEDED ON |
| | ALL THREE ELEVATIONS.PLEASE CORRECT. |
| | |
| | 7)PROVIDE 2 COMPLETED CITY OF W.P.B. |
| | DESIGN CERTIFICATION FORMS. |
| | |
| | 8)PROVIDE STATE REQUIRED ENERGY |
| | CALCULATIONS INCLUDING MANUAL "J" FOR |
| | NEW ADDITION. |
| | |
| | 9)SAFETY GLASS REQUIRED IN BATH ROOM |
| | WINDOW 97 SBC 2405.2 |
| | |
| | 10)PROVIDE CEILING HEIGHT ELEVATIONS FOR |
| | ADDITION AND EXISTING STRUCTURE. |
| | |
| | 11)SPECIFY WIDTH OF FOOTINGS ON PLANS. |
| | BOTTOM OF FOOTING MUST BE A MINIMUM OF |
| | 12" BELOW FINISH GRADE.97SBC 1804 |
| | |
| | 12)PROVIDE ATTIC ACCESS IF CLEAR HEIGHT |
| | OF ATTIC SPACE,MEASURED AT THE ROOF PEAK |
| | IS 24" OR MORE. |
| | |
| | 13)SPECIFY SPECIFIC CONNECTORS USED TO |
| | ANCHOR TRUSSES TO WALLS. |
| | |
| | 14)PERFORM CALCULATIONS TO DETERMINE |
| | WINDLOADS ON ROOF TRUSSES AND PROVIDE |
| | UPLIFT ON PLANS. |
| | |
| | 15)PROVIDE DETAILS FOR CONNECTION OF |
| | ADDITION ROOF TO EXISTING ROOF. |
| | |
| | 16)PROVIDE DETAILS FOR CONNECTION OF |
| | ADDITION FOOTINGS AND WALLS TO EXISTING |
| | STRUCTURE. |
| | |
| | 17)PROVIDE FOUNDATION PLAN FOR ADDITION. |
| | |
| | 18)PROVIDE WINDOW AND DOOR BUCK DETAILS |
| | FOR WIND LOAD RESISTANCE. |
| | |
| | 19)PROVIDE WEST ELEVATION OF EXISTING |
| | STRUCTURE SHOWING ALL WINDOW AND DOOR |
| | OPENINGS TO VERIFY TABLE 6OO COMPLIANCE |
| | OR NON-COMPLIANCE OF ADDITION. |