| Plan Review Notes For Permit 00071531 |
| Permit Number |
00071531 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | FOR THE EXISTING SERVICE PER ART 220-3-C | | | -1. | | | | | | 2)NOTE: PROVIDE A REVISED PANEL SCHEDULE | | | TO INCLUDE THE NEW CIRCUITS BEING ADDED | | | AND THE REQ`D DEDICATED BATH CIRCUIT(S) | | | PER 210-11-C-3. | | | | | | 3)NOTE: PLEASE NOTE MISSING RECEPT.PER | | | 210-52 | | | | | | 4)NOTE: PLEASE NOTE THERE WILL BE A | | | SMOKE DETECTOR REQ`D IN COMMON AREA OF | | | ADDITION. PER NFPA-72 2-2.1.1.1 | | | | | | 5)NOTE: PLEASE SHOW THE REQ`D WP/GFI | | | RECEPT. ON THE OUTSIDE OF ADDITION. | | | PER 210-52E | | | | | | 6)NOTE: PLEASE SHOW ALL NEW BLDG. STEEL | | | AS BEING BONDED TO GROUNDING ELECTRODE | | | SYSTEM. PER 250-50 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS. | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|