Plan Review Notes
Plan Review Notes For Permit 00071531
Permit Number 00071531
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR THE EXISTING SERVICE PER ART 220-3-C
 -1.
  
 2)NOTE: PROVIDE A REVISED PANEL SCHEDULE
 TO INCLUDE THE NEW CIRCUITS BEING ADDED
 AND THE REQ`D DEDICATED BATH CIRCUIT(S)
 PER 210-11-C-3.
  
 3)NOTE: PLEASE NOTE MISSING RECEPT.PER
 210-52
  
 4)NOTE: PLEASE NOTE THERE WILL BE A
 SMOKE DETECTOR REQ`D IN COMMON AREA OF
 ADDITION. PER NFPA-72 2-2.1.1.1
  
 5)NOTE: PLEASE SHOW THE REQ`D WP/GFI
 RECEPT. ON THE OUTSIDE OF ADDITION.
 PER 210-52E
  
 6)NOTE: PLEASE SHOW ALL NEW BLDG. STEEL
 AS BEING BONDED TO GROUNDING ELECTRODE
 SYSTEM. PER 250-50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS.
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372