| Plan Review Notes For Permit 00071468 |
| Permit Number |
00071468 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT THE AIC RATING | | | FOR ALL EQUIPMENT AS ASKED FOR ON THE | | | PREVIOUS REVIEW. MAIN/ PANEL/ BRKRS ARE | | | ALL TO BE RATED FOR THE AVAILABLE FAULT | | | CURRENT. | | | | | | 2)NOTE: PER F.A.C. ALL CHANGES ON PLANS | | | ARE TO BE SIGNED AND DATED BY THE ENGIN- | | | -EER OF RECORD. | | | | | | 3)NOTE: PLEASE NOTE THAT UNDER THE F.A.C | | | 61G15-23.002 PLANS MUST CONTAIN THE | | | TITLE BLOCK OF ENGINEER OF RECORD. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FORREVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|