| Plan Review Notes For Permit 00071468 |
| Permit Number |
00071468 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: | | | | | | | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATING OF | | | EQUIPMENT MAINS. MAINS/PANELS ARE TO BE | | | RATED FOR THE AVAILBLE FAULT CURRENT. | | | PER 110-9/215-5 | | | | | | 3)NOTE: GFI OUTLET REQ`D FOR A/C CU. | | | | | | 4)NOTE: PLEASE ADD SD PER NFPA-72 2-2.1. | | | 1.1. | | | | | | 5)NOTE: PLEASE ADD BATH CIRCUIT PER | | | 210-11-C-3../215-5 | | | | | | PLEASE SUBMIT ALL THE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|