2001-01-08 00:00:00PASSED WITH PROVISOS
 1. COMPLETE NEW SIDEWALK ALONG SITE.
 2. BACKFLOWS MUST BELOCATED OUTSIDE OF W
 ALL.
 3. FIRE HYDRANT MUST BE INSTALLED AND LO
 CATED PER CITY OF WEST PALM BEACH STANDA
 RD DETAIL.561-659-8040 EXT. 2303
 4. A HEALTH DEPARTMENT PERMIT IS REQUIRE
 D THROUGH PUBLIC UTILITIES ENGINEERING S
 ERVICES DIVISION.
 MANNY GONZALEZ 561-659-8040 EXT. 2306
 5. MISSING VALVE DETAIL AND SAMPLE POINT
 DETAIL. CALL JANICE A 561 659 8040EX2303
 6. WATERMAIN MUST BE DIP CEMENT-LINED
 CLASS 52.
 7. ANY CURB OR SIDEWALK THAT WILL BE CUT
 OR DAMAGED DURING INSTALLATION OR CONS-
 TRUCTION OF THE WATERMAIN MUST BE REPLAC
 ED TO EQUAL OR BETTER CONDITION.
 8. FIRE HYDRANT LOCATION MUST BE APPROVE
 D BY FIRE DEPARTMENT PRIOR TO FINAL
 APPROVAL OF WATERMAIN.
 9. MUST MAINTAIN 18" MIMIMUM CLEARANCE
 BETWEEN WATER AND SEWER.
 10. TO WHAT ADDRESS DO CHARGES WILL
 APPLY 420 OR 424 HAMPTON.PLEASE
 CONTACT MANNY.