Plan Review Notes
Plan Review Notes For Permit 00071404
Permit Number 00071404
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)A WATER USE PERMIT FOR THE IRRIGATION
 SYSTEM IS REQD.FROM SO.FLA.WATER MNGMT.
 DISTRICT PER FLA.STATUTE 373.219.A WELL
 DRILLING WILL ALSO BE REQD.
  
 2)A PERMIT FOR THE WELL WILL ALSO BE
 REQD.FROM FLA.DEPT.OF HEALTH.COUNTYWIDE
 AMENDMENTS TO SPC SEC.101.4.7.
  
 3)SHT.M-3-CONDENSATE DRAIN CANNOT
 CONNECT DIRECTLY TO THE STORM DRAINAGE
 SYSTEM.CONNECTION SHALL BE MADE BY
 INDIRECT WASTE AND ON EXTERIOR.SPC 804.3
 SMC SEC.304.8.3.
  
 4)HANDICAP DRINKING FOUNTAIN SHALL
 COMPLY W/FACBC SEC.4.1.3.(10)(A).
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLE BENDING OR STOOPING.
  
 5)GRAB BAR ALONGSIDE WATER CLOSET SHALL
 BE 42"PER FACBC SEC.4.16.4,4.26,FIG.29.
  
 CALL 561-659-8096 IF YOU HAVE ANY
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.