| Plan Review Notes For Permit 00071404 |
| Permit Number |
00071404 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) HOW DOES THE FIRE RESCUE DEPARTMENT | | | ENTER THE GATED AREA TO PROVIDE | | | SERVICES. FIRE AND PARAMEDICAL UNITS | | | MUST BE ABLE TO ENTER THE PARKING AREA. | | | 2) BUILDING ADDRESS TO MEET CITY CODE | | | REQUIREMENTS. | | | 3) PROVIDE MORE INFORMATION ON THE | | | PRE-ACTION FIRE SPRINKLER SYSTEM PLANNED | | | FOR USE. | | | 4) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | DRAWINGS. CUT SHEETS ON DEVICES PLANNED | | | FOR USE ARE TO BE PROVIDED. A WIRING | | | DIAGRAM AND BATTERY CALCULATIONS ARE | | | TO BE PROVIDED. A SEPARATE PLAN AND | | | PERMIT ARE REQUIRED. | | | 5) CAN THE EXIT DOORS LOCATED AT THE | | | STAIRTOWERS ON LEVEL TWO SWING IN THE | | | DIRECTION OF EXIT TRAVEL. | | | 6) PROVIDE MORE DETAILS ON GENERATOR. |
|