Plan Review Notes
Plan Review Notes For Permit 00071404
Permit Number 00071404
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) HOW DOES THE FIRE RESCUE DEPARTMENT
 ENTER THE GATED AREA TO PROVIDE
 SERVICES. FIRE AND PARAMEDICAL UNITS
 MUST BE ABLE TO ENTER THE PARKING AREA.
 2) BUILDING ADDRESS TO MEET CITY CODE
 REQUIREMENTS.
 3) PROVIDE MORE INFORMATION ON THE
 PRE-ACTION FIRE SPRINKLER SYSTEM PLANNED
 FOR USE.
 4) PROVIDE COMPLETE FIRE ALARM SYSTEM
 DRAWINGS. CUT SHEETS ON DEVICES PLANNED
 FOR USE ARE TO BE PROVIDED. A WIRING
 DIAGRAM AND BATTERY CALCULATIONS ARE
 TO BE PROVIDED. A SEPARATE PLAN AND
 PERMIT ARE REQUIRED.
 5) CAN THE EXIT DOORS LOCATED AT THE
 STAIRTOWERS ON LEVEL TWO SWING IN THE
 DIRECTION OF EXIT TRAVEL.
 6) PROVIDE MORE DETAILS ON GENERATOR.