2001-01-08 00:00:00UPON REVIEWING THE ABOVE REFERENCED
 PROJECT THE FOLLOWING ITEMS WILL NEED
 TO BE ADDRESSED:
  
 SHEET C2 CALLS OUT REMOVING DRIVEWAY
 ENTRANCES THAT ARE NOT NEEDED, PLACE
 A NOTE THAT CONTRACTOR SHALL REPLACE
 DRIVEWAYS TO BE REMOVED WITH NEW SIDE-
 WALK AND CURB TO MATCH EXISTING (TYP)
  
 SHEET C3.00
 A POLLUTION PREVENTION PLAN MUST BE
 PROVIDED SHOWING A SILT FENCE AROUND
 THE ENTIRE SITE AND A SILT FENCE INSTALL
 ATION DETAIL.THIS PLAN MUST CONTAIN
 THE SITE INFORMATION AS SHOWN ON SHEET
 C-1.00. YOU MAY COMBINE THE SITE PLAN
 AND POLLUTION CONTROL PLAN TOGETHER.
 (SITE PLAN AND POLLUTION CONTROL PLAN)
  
 SHEET C-4.00
 A CLEAN-OUT IS REQUIRED AT THE POINT OF
 SEWER ENTERING THE BUILDING AND AT THE
 BACK OF SIDEWALK. CONTRACTOR SHALL
 VERIFY THE CLEAN-OUT IS IN PLACE OR
 CUT ONE INTO EXISTING SEWER SERVICE.
  
 SHEET C-4.00
 THE CITY OF WEST PALM BEACH DOES NOT
 ALLOW 3" FIRELINES.IT MUST BE A 2"
 WITH A 2" VALVE. THE OTHER OPTION WOULD
 BE TO RUN A NEW 8" WM ALONG HAMPTON OFF
 DIXIE HWY. TO THEN SERVE THIS BUILDING
 WITH A 4" FIRELINE.
  
 SHEET C-4.00
 A VALVE MUST BE PROVIDED TO SEPERATE
 PRIVATE FIRE LINE AND WATER SERVICE LINE
 SO THAT WHEN ONE IS DOWN FOR SERVICE
 THE OTHER WOULD BE IN OPERATION.
  
 SHEET C-4.00
 PLACE METER IN SIDEWALK WITH LOCKING LID
 AND TOUCHREAD OPTION.
  
 GENERAL COMMENT:
 PLEASE LABEL PROPERTY LINE OR SHOWN IN A
 DIFFERENT LINE TYPE.
  
 IN STANDARD DETAIL SHEET PLEASE
 PROVIDE THE FOLLOWING:
 CWPB TYPICAL TRENCH DETAIL OR PAVEMENT
 REPLACEMENT DETAIL.
  
 GENERAL NOTES:
 1.A SEPARATE IRRIGATION METER IS
 SUGGESTED TO SAVE ON THE MONTHLY
 WATER BILL. AN APPROVED BACKFLOW
 PREVENTER WILL NEED TO BE INSTALLED
 ON THIS LINE.
  
 2.NO WATER AND OR SANITARY LINES CAN BE
 LAID, IF PLANS ARE NOT SUBMITTED TO US,
 SEPARATELY AND PRIOR TO SUBMITTAL FOR A
 BUILDING PERMIT FROM BUILDING AND ZONING
 ANDSERVICE WILL NOT BE GRANTED.
 SUBMITT TO MANNY GONZALEZ
 PUBLIC UTILITIES PROJECT SPECIALIST
 1000 45TH STREET
 WEST PALM BEACH, FL 33415
 (561) 659-8040 EXT. 2306
 (2 SETS MINIMUM)
  
 3.ALL BROKEN SIDEWALKS ALONG THE PROPERT
 Y MUST BE REPLACED.
  
 4.ALL DRIVEWAYS THAT WILL NOT BE USED MU
 ST REMOVED AND THE REGULAR CURBS
 (&GUTTERS)MUST BE REPLACED.
  
 5.ALL BROKEN UP CURBS (& GUTTERS)
 MUST BE REPLACED.
  
 6.ALL DRIVEWAY APPROACHES MUST BE (AT A
 MINIMUM) PER CITY STANDARD DETAIL INDEX.
  
 7.ALL GRADES FOR CITY SIDEWALKS WILL BE
 SET BY THE CITY SURVEY CREW, CALL 659-80
 40ASK FOR ED RYAN TO SET UP AN
 APPOINTMENT.
  
 8. NO DUMPSTER IS SHOWN. THIS SITE WILL
 NOT GENERATE TRASH>????
  
 POLLUTION PREVENTION PLAN MUST BE KEPT
 ON SITE AT ALL TIMES DURING CONSTRUCTION
 THE PLAN SHALL BE INSTALLED IN THE FIELD
 PRIOR TO ANY EARTHWORK.