2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SEE PANEL "L1" THIS REQ`S
 A MCB ON THE LOAD SIDE OF TRANSFORMER
 BEING A SEPARATELY DERIVED SYSTEM.
  
 2)NOTE: PLEASE PROVIDE MORE DETAIL ON
 LOAD CALCULAITONS. SQ.FT/CONTINUOUS LOAD
 -S AT 125%.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  