2001-01-08 00:00:00*****************PROVISO****************
 1)SHT.E-P3.01 SHOWS CD AS 1 1/4"AND SHT.
 E-P5.01 SHOWS 1".COMPLY W/SMC SEC.
 304.8.4.
  
 2)FIXTURE UNIT LOAD ON STACKS IS
 INCORRECT.COMPLY W/SPC 713.1 FOR F.U.
 LOAD VALUE.
  
 3)CLEANOUTS ARE REQD.IN WASTE AND SOIL
 STACKS.COMPLY W/SPC SEC.710.2.1.(5),
 710.2.4(1)(2).
  
 4)SHT.E-P5.01-WATER ISOMETRIC-NOTES
 "FOR CONT.SEE TYPICAL WATER ISOMETRIC
 BELOW"AND A WATER ISOMETRIC IS NOT
 SHOWN.CLARIFY.
  
 5)PROTECTION OF THE WATER DISTRIBUTION
 SYSTEM AGAINST HAZARD AND NOISE SHALL
 COMPLY W/SPC SEC.607.8.1-607.8.3.
  
 THE ABOVE INFORMATION SHALL BE PROVIDED
 PRIOR TO PLUMBING INSPECTION.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
  