| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *****************PROVISO**************** | | | 1)SHT.E-P3.01 SHOWS CD AS 1 1/4"AND SHT. | | | E-P5.01 SHOWS 1".COMPLY W/SMC SEC. | | | 304.8.4. | | | | | | 2)FIXTURE UNIT LOAD ON STACKS IS | | | INCORRECT.COMPLY W/SPC 713.1 FOR F.U. | | | LOAD VALUE. | | | | | | 3)CLEANOUTS ARE REQD.IN WASTE AND SOIL | | | STACKS.COMPLY W/SPC SEC.710.2.1.(5), | | | 710.2.4(1)(2). | | | | | | 4)SHT.E-P5.01-WATER ISOMETRIC-NOTES | | | "FOR CONT.SEE TYPICAL WATER ISOMETRIC | | | BELOW"AND A WATER ISOMETRIC IS NOT | | | SHOWN.CLARIFY. | | | | | | 5)PROTECTION OF THE WATER DISTRIBUTION | | | SYSTEM AGAINST HAZARD AND NOISE SHALL | | | COMPLY W/SPC SEC.607.8.1-607.8.3. | | | | | | THE ABOVE INFORMATION SHALL BE PROVIDED | | | PRIOR TO PLUMBING INSPECTION. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|