Plan Review Notes
Plan Review Notes For Permit 00071380
Permit Number 00071380
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) APARTMENT DOORS TO BE AT LEAST 20
 MINUTE FIRE RATED EQUIPPED WITH SELF
 CLOSING DEVICES.
 2) SMOKE DETECTORS INSTALLED WITHIN THE
 APARTMENTS, WHEN ACTIVATED SHALL BE
 AUDIBLE IN THE SLEEPING ROOMS OF THAT
 UNIT. THESE DETECTORS SHALL BE INSTALLED
 A MINIMUM OF AT LEAST THREE FEET FROM
 AIR CONDITIONER DIFFUSERS.
 3) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL ELECTRICAL, MECHANICAL, STORAGE
 ROOMS, AND VERTICAL SHAFTS.
 4) SUBMIT COMPLETE FIRE ALARM SYSTEM
 DRAWINGS FOR THE BUILDING. CUT SHEETS
 AND WIRING DIAGRAM ARE TO BE SUBMITTED.
 5) ELEVATOR TO COMPLY WITH ANSI A17.1
 6) PORTABLE FIRE EXTINGUISHERS REQUIRED.
 7) KNOX-BOX NEEDED FOR BUILDING.