| Plan Review Notes For Permit 00071380 |
| Permit Number |
00071380 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) APARTMENT DOORS TO BE AT LEAST 20 | | | MINUTE FIRE RATED EQUIPPED WITH SELF | | | CLOSING DEVICES. | | | 2) SMOKE DETECTORS INSTALLED WITHIN THE | | | APARTMENTS, WHEN ACTIVATED SHALL BE | | | AUDIBLE IN THE SLEEPING ROOMS OF THAT | | | UNIT. THESE DETECTORS SHALL BE INSTALLED | | | A MINIMUM OF AT LEAST THREE FEET FROM | | | AIR CONDITIONER DIFFUSERS. | | | 3) ENTIRE BUILDING IS TO BE COMPLETELY | | | FIRE SPRINKLER PROTECTED. THIS INCLUDES | | | ALL ELECTRICAL, MECHANICAL, STORAGE | | | ROOMS, AND VERTICAL SHAFTS. | | | 4) SUBMIT COMPLETE FIRE ALARM SYSTEM | | | DRAWINGS FOR THE BUILDING. CUT SHEETS | | | AND WIRING DIAGRAM ARE TO BE SUBMITTED. | | | 5) ELEVATOR TO COMPLY WITH ANSI A17.1 | | | 6) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | 7) KNOX-BOX NEEDED FOR BUILDING. |
|