| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | SHOWING ALL CONTINUOUS LOADS AT 125%. | | | LIGHTING ETC. | | | | | | 2)NOTE: PLEASE INCLUDE BLDG STEEL AS | | | PART OF THE GROUNDING ELECTRODE SYSTEM. | | | SEE 250-50 OF THE NEC. ALSO SIZED PER | | | 250-66. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|