| Plan Review Notes For Permit 00071365 |
| Permit Number |
00071365 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED PER TONY MARCELLO 8-30-00 | | | | | | 1)PROVIDE 1 HR. RATED GLASS BLOCK IN THE | | | "O" WALL. | | | | | | 2)FIXED BUTT GLASS SHALL COMPLY WITH | | | SEC. 2406.2 SUBMIT DATA AS PER THIS | | | SECTION. | | | | | | 3)PROVIDE ONE BATHROOM WITH ONE 29"CLEAR | | | DOOR OPENING.SEC. 4.22.2 FL ACCESSIBIL- | | | ITY CODE | | | | | | 4)PROVIDE METRO-DADE OR SBCCI PRODUCT | | | APPROVALS FOR ROOF TILE. | | | | | | 5)FOAM TRIM MUST COMPLY WITH SEC. 2603 | | | OF THE 97 SBC. | | | | | | 6)BROWARD CO.PRODUCT APPROVAL FORM IS | | | NOT ACCEPTABLE. PROVIDE CURRENT METRO- | | | DADE OR SBCCI PRODUCT APPROVALS OR SITE | | | SPECIFIC ENGINEERING. |
|