| 2001-01-08 00:00:00 | DENIED BY TONY MARCELLO 8-30-00 | | | | | | 1)PROVIDE 1 HR. RATED GLASS BLOCK IN THE | | | "O" WALL SECTION | | | 2)ONE BATHROOM DOOR MUST COMPLY WITH SEC | | | 4.22.2 OF THE FLORIDA ACCESSIBILITY CODE | | | A 29" CLEAR OPENING. | | | 3)THE FOAM TRIM MUST COMPLY WITH SEC. | | | 2603 OF THE 97 SBC. | | | 4)BROWARD CO. PRODUCT APPROVAL FORMS ARE | | | NOT ACCEPTABLE.PROVIDE METRO-DADE OR | | | SBCCI PRODUCT APPROVALS OR SITE SPECIFIC | | | ENGINEERING ON CITY OF W.P.B. PRODUCT | | | APPROVAL FORMS. |
|