| Plan Review Notes For Permit 00071334 |
| Permit Number |
00071334 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-03-07 00:00:00 | CHANGED AHU - SUPPLY AIR WENT FROM 800 | | | CFM TO 1200 CFM, O.A. STAYED AT 140 CFM | | | AND AIR BALANCE TABLE STILL SHOWS 800 | | | CFMBEING SUPPLIED AND O.A. AT 140. | | | SCHEDULES NEED TO CORRELATE. |
|