Plan Review Notes
Plan Review Notes For Permit 00071327
Permit Number 00071327
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** PROVISO **************
  
 1)NOTE: PLEASE PROVIDE AIC RATINGS
 OF ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS. MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9
 215-5.
  
 2)NOTE: PLEASE SUBMIT COMPLETED PANEL
 SCHEDULE. 215-5
  
 3)NOTE: PLEASE NOTE 210-11-C-3 FOR THE
 REQ`D BATH(S) CIRCUIT(S). PLEASE LIST ON
 PANEL SCHEDULE.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE FINAL ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372