| 2001-01-08 00:00:00 | PROVISO: | | | THE EXCEPTION FOR NO FIRE DAMPER IF DUCT | | | IS UNDER 100 SQ.IN. MUST MEET ALL FOUR | | | PARTS OF THE EXCEPTION, INCLUDING | | | METAL GAUGE, EXTENDING 5 FEET ON BOTH | | | SIDE OF THE RATED WALL AND THE DUCT | | | SHALL BE INSTALLED ABOVE A CEILING, PER | | | 1997 SMC 610 |
|