Plan Review Notes
Plan Review Notes For Permit 00071272
Permit Number 00071272
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 THE EXCEPTION FOR NO FIRE DAMPER IF DUCT
 IS UNDER 100 SQ.IN. MUST MEET ALL FOUR
 PARTS OF THE EXCEPTION, INCLUDING
 METAL GAUGE, EXTENDING 5 FEET ON BOTH
 SIDE OF THE RATED WALL AND THE DUCT
 SHALL BE INSTALLED ABOVE A CEILING, PER
 1997 SMC 610