Plan Review Notes
Plan Review Notes For Permit 00071272
Permit Number 00071272
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00****************UNSAT ** ***************
  
 1)NOTE:PLEASE SHOW THE REQ`D SHOW WINDOW
 RECEPTS PER 210-62. AND LOAD PER 220-3-B
 -7-B
  
 2)NOTE: PLEASE CHECK LIGHTING LOAD SHOWN
 FOR A-1. THIS DOES NOT CORRELATE WITH
 FIXTURE COUNT.
  
 3)NOTE:PLEASE NOTE THAT YOU SHOW A 60AMP
 DISCONNECT WITH 100AMP OCP FROM TENANT.?
  
 4)NOTE: PLEASE SEE ART 450-3-B FOR OCP
 CLARIFICATION.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
  
 561-659-8096 EXT 8372