Plan Review Notes
Plan Review Notes For Permit 00071266
Permit Number 00071266
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED:
 1.REQUIRES ENERGY CALCULATIONS PER
 FLORIDA ENERGY CODE...
 2.PROVIDE AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2......
 3.PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 4.SHOW AND PROVIDE DAMPERS ON PLANS AS R
 REQUIRED PER 610.1.2....
 5.REQUIRED DUCT MOUNTING DETAIL.
 6.PROVIDE MOUNTING DETAIL OF THE AHU
 SYSTEM ON PLANS...