| Plan Review Notes For Permit 00071266 |
| Permit Number |
00071266 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED: | | | 1.REQUIRES ENERGY CALCULATIONS PER | | | FLORIDA ENERGY CODE... | | | 2.PROVIDE AIR BALANCE SCHEDULE AS PER | | | 1997 SMC 501.2...... | | | 3.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 4.SHOW AND PROVIDE DAMPERS ON PLANS AS R | | | REQUIRED PER 610.1.2.... | | | 5.REQUIRED DUCT MOUNTING DETAIL. | | | 6.PROVIDE MOUNTING DETAIL OF THE AHU | | | SYSTEM ON PLANS... |
|