| Plan Review Notes For Permit 00071266 |
| Permit Number |
00071266 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) WRONG FIRE CODE REFERENCE IN CODE | | | DATA BOX. SHOULD READ NFPA 101, 1985 | | | INSTEAD OF NFPA 101, 1991. | | | 2) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | IN PLANS. | | | 3) PROVIDE PLANS AND PERMIT FOR FIRE | | | ALARM EQUIPMENT SHOWN ON DRAWINGS. | | | 4) CHEMICAL TYPE FIRE EXTINGUISHERS | | | SHOWN ON FIXTURE PLAN TO BE AT LEAST | | | 5LBS. WITH A RATING OF AT LEAST | | | 2A 10BC. | | | 5) DEMISING RATED WALL ASSEMBLIES TO | | | BE COMPLETED ON BOTH SIDES OF THE | | | WALL PRIOR TO OCCUPANCY. |
|