Plan Review Notes
Plan Review Notes For Permit 00071266
Permit Number 00071266
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE COMPLETE LOAD CALCULATION
 -S SHOW ALL CONTINUOUS LOADS AT 125%
 (LIGHTING ETC).PLEASE INCLUDE LOADS FOR
 SHOW WINDOW RECEPTS AND TRACK LIGHTING
 PER 220-12-A/B
  
 2)NOTE: PLEASE SEE ART 450-3-B FOR OCP
 OF TRANSFORMERS PRIM/SEC.
  
 3)NOTE:PLEASE SUBMIT AIC RATINGS FOR ALL
 EQUIPMENT/MAINS/ PANELS. MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT PER ART;
 110-9.
  
 4)NOTE: IS CIRCUIT #4 SHOWN AS ENTRY
 LIGHTS ON PANEL SCHEDULE CORRECT?
 PLEASE CLARIFY.
  
 5)NOTE: PLEASE SEE THAT OUTLET SPACING
 TO MEET LOCAL CODE IN STORAGE AREA.
 210-50 EVERY 20` OF WALL.
  
 6)NOTE: PLEASE SEE 210-62 FOR SHOW WIN-
 -DOW OUTLETS .
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
  
 561-659-8096 EXT 8372