| Plan Review Notes For Permit 00071266 |
| Permit Number |
00071266 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE COMPLETE LOAD CALCULATION | | | -S SHOW ALL CONTINUOUS LOADS AT 125% | | | (LIGHTING ETC).PLEASE INCLUDE LOADS FOR | | | SHOW WINDOW RECEPTS AND TRACK LIGHTING | | | PER 220-12-A/B | | | | | | 2)NOTE: PLEASE SEE ART 450-3-B FOR OCP | | | OF TRANSFORMERS PRIM/SEC. | | | | | | 3)NOTE:PLEASE SUBMIT AIC RATINGS FOR ALL | | | EQUIPMENT/MAINS/ PANELS. MUST BE RATED | | | FOR THE AVAILABLE FAULT CURRENT PER ART; | | | 110-9. | | | | | | 4)NOTE: IS CIRCUIT #4 SHOWN AS ENTRY | | | LIGHTS ON PANEL SCHEDULE CORRECT? | | | PLEASE CLARIFY. | | | | | | 5)NOTE: PLEASE SEE THAT OUTLET SPACING | | | TO MEET LOCAL CODE IN STORAGE AREA. | | | 210-50 EVERY 20` OF WALL. | | | | | | 6)NOTE: PLEASE SEE 210-62 FOR SHOW WIN- | | | -DOW OUTLETS . | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | | | | 561-659-8096 EXT 8372 |
|