Plan Review Notes
Plan Review Notes For Permit 00071225
Permit Number 00071225
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 FAN SHUTDOWN REQUIRED FOR AHU PER NFPA
 90A 4.4.4.2 AND 4.4.4.3...
  
 PROVIDE OUTSIDE AIR AS PER ASHRAE 62-89.
 CONTRACTOR INDICATES OVERHEAD DOORS OPEN
 WHEN OCCUPIED
 CONDENSATE TO BE PER 1997 SMC TO PERMI-
 ABLE LOCATION AND OVERFLOW PROTECTION
 REQUIRED