| Plan Review Notes For Permit 00071225 |
| Permit Number |
00071225 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | FAN SHUTDOWN REQUIRED FOR AHU PER NFPA | | | 90A 4.4.4.2 AND 4.4.4.3... | | | | | | PROVIDE OUTSIDE AIR AS PER ASHRAE 62-89. | | | CONTRACTOR INDICATES OVERHEAD DOORS OPEN | | | WHEN OCCUPIED | | | CONDENSATE TO BE PER 1997 SMC TO PERMI- | | | ABLE LOCATION AND OVERFLOW PROTECTION | | | REQUIRED |
|